Ex 5/7/11 rt system – MGE UPS Systems EX 7RT User Manual

Page 24

Advertising
background image

1.5.8

CLA Module (Long backup time charger)

(Part number 86004)

Extended back-up time (up to 8 hours at full load) requires a high power battery cabinet connected to the EX
5/7/11RT via the CLA module.

IMPORTANT

The CLA can not be used to charge the battery module (EXB). It is designed to charge the
customer provided high power battery cabinet.

Figure 1-12: Connection for CLA Module and EX 5/7/11 RT.

Table 5: Battery backup time chart.

Battery Backup Time

Recommended Batteries

EX 5RT

EX 7RT

EX 11RT

2 hours

50 Ah

65 Ah

100 Ah

4 hours

100 Ah

130 Ah

200 Ah

8 hours

200 Ah

200 Ah

400 Ah

Total battery voltage : 240 VDC (20 x 12VDC, one string).

The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalization section 3.2.

EX 5/7/11 RT System

Introduction

1 — 12

86-86000-00 A01


EX 5RT /
EX 7RT /
EX 11RT

~

50A

(cable not included)

Typical High Power
Battery Cabinet

(not included)

Utility

AC Source

(cable not included)

(see section 2.10 for cable

connection information)

www

.mge

ups.

com

E X

R T

Tra

nsfor

mer

CLA Module Contents

CLA

Tower Stand Expanders

CLA Documentation

Battery Detection Cable

Battery Power Cable

Stabilizer Bracket