Installation and user manual – MGE UPS Systems EX 7RT User Manual

Page 41

Advertising
background image

Installation and User Manual

2.8.4

System Connections with Separate Normal and Bypass AC Sources

CAUTION:

This installation requires 2 AC input source with Line, Neutral plus Ground,
(200-240VAC). Neutral points are connected together inside the UPS.

Figure 2-15: Normal AC Input, Bypass AC, and Output Cables Installation.

Installation

2 — 17

86-86000-00 A01

Proceed as follows:

1.

Remove the cover plate under the I/O Box. Loosen
the terminal blocks L1 and L3, and remove the
jumper.

CAUTION:

Always connect the

earth ground wire first.

2.

See section 2.8.1 and I/O Box terminal diagram for
installation of Normal AC Input, Bypass AC
source, and Output cable with different wire style.

3.

Reinstall the cover plate under the I/O Box with
four screws.

4.

Secure the I/O Box to the power module using
three screws.

See section 2.8.3 for connecting EX RT
Transformer, if applicable.

4

Card Settin

g

s

RS232 Download

66074

UPS

data

Reset

100 10

1 2

ON

ETHERNET

IP=

MAC=00E0D

8

FF

8

55E

1

3

Output

Bypass

Normal

L1

L3

OFF

O

OFF

O

OFF

O

To Step-Down

Transformer

(if applicable)

2