Appendix

5.0

Electrical Specifications

5.1

System Input/Output Power Ratings

Table 5-1: EX 5/7/11 RT Input and Output Characteristics.

Source

Voltage

Frequency

Normal AC Source

208 to 240 Volts AC

40 to 70 Hz

Bypass AC Source

208 to 240 Volts AC*

48 to 52 Hz**

Load Output

120/240Vac Volts AC

50/60 Hz autoranging

(120/208/240Vac

(or frequency converter)

are possible with
transformer module)

(*): depends on output voltage setting, can be modified by software.

(**): set to +/- 4% by default, (1,2,4,8% are possible values), can be modified by software.

5.2

System Overload Characteristics

Figure 5-1: Power supplied as a function of input voltage (left), and Permissible UPS overloads as a function of time (right).

5.3

System Backup Characteristics

Table 5-2: Back-up Time ( in minutes).

System

Load Percentage

30%

50%

70%

100%

Standard 11kVA

25

14

9

5

Standard 11kVA + 1 EXB

61

30

20

14

Standard 11kVA + 2 EXB

96

53

34

22

Standard 11kVA + 3 EXB

135

84

51

30

Standard 11kVA + 4 EXB

172

102

67

42

Standard 11kVA + 5 EXB

201

113

87

53

Standard 7kVA

37

21

12

7

Standard 7kVA + 1 EXB

80

53

30

20

Standard 7kVA + 2 EXB

124

83

55

32

Standard 7kVA + 3 EXB

185

108

75

45

Standard 7kVA + 4 EXB

245

132

98

57

Standard 7kVA + 5 EXB

287

164

118

72

Standard 5kVA

37

31

21

12

Standard 5kVA + 1 EXB

90

70

53

30

Standard 5kVA + 2 EXB

140

112

83

55

Standard 5kVA + 3 EXB

185

156

108

75

Standard 5kVA + 4 EXB

255

207

132

98

Standard 5kVA + 5 EXB

306

260

164

118

Appendix

5 — 1

86-86000-00 A01

100%

70%

120V

U

160V

280V

Load Percentage

1.02

0.5s

t

30s

1.1

1.25

1.5

60s

120s

Load Percentage