Table 3-1: Local Settings.

Display

Factory setting

Options

Language

English

French, Spanish, German, Italian

Date / time format

International format

US format

(DD-MM-YYYY/HH:MM)

(MM-DD-YYYY/HH:MM AM/PM)

Date / time change

GMT (Greenwich Mean Time)

MM-DD-YYYY/HH:MM adjustable

Audible alarm

Quick beeps

Slow beeps

Table 3-2: Output features.

Display

Factory setting

Options

Comments

Output voltage

208 Volts AC

200/208/220/230/240/250

Frequency converter

Disabled

Enabled

Bypass AC source disabled

Output frequency

Auto ranging

50/60 Hz

User selectable under
frequency converter mode

Eco mode

Disabled

Enabled

See glossary

Hot standby

Disabled

Enabled

Full redundancy (see Figure 3-3)

Operating mode

IT Network

Industrial

(*) See Section 4.1

Bypass

When bypass OK (**)

When bypass NOK (**)

(*)

Transfer

Interrupt time

10 ms

10 to 200 ms

Interrupt time calibration during

(by steps of 10 ms)

during load transfer on
Bypass AC source
out of tolerances

Overload level

102%

50/70%

(*) : - Select "IT Network" for computer loads.

- Select "Industrial" when bypass NOK in case of absolute need for service continuity (with potential

10 ms interrupt).

(**) UPS will switch to Bypass AC Source if it is within the set tolerances.

Figure 3-3: Configuration used to provide full redundancy (2N) to critical loads.

Operation

3 — 3

86-86000-00 A01

Utility

AC Source

NORMAL AC

LOAD

BYPASS AC

NORMAL AC

Protective Device

Protective Device

Full redundancy configuration
offers better protection to
critical load, whereas the first
UPS acts as the Bypass AC
Source for the second UPS.