Table 5-3: Battery Recharge time to recover 90% of the rated backup time after discharge at full load.

Configuration for

Configuration for

Configuration for

2 hours backup time

4 hours backup time

8 hours backup time

EX 5

7 hours

15 hours

24 hours

EX 7

5 hours

12 hours

20 hours

EX 11

7 hours

15 hours

24 hours

5.4

System Short Circuit Protection

Short circuit current provided by EX 5/7/11RT in normal or battery mode:

EX5/7 RT

110A for 80ms

EX11 RT

190A for 80ms

5.5

Accessories Electrical Characteristics

EX RT Transformer

Nominal power

11 kVA

Nominal current

63 A

Input voltage

208-240Vac

Output Voltage

120/208/240Vac

Frequency

50/60 Hz (+/-10%)

Isolation (EN 61558-1-2-4)

3.75 kV / 5 M ohms

Operating temperature

From 0° to +40°C

Max. operating rel. humidity

95%

Derating / altitude

Pn-10% > 1000 m

Dimensions HxWxD (tower)

17.5 x 5.15 x 25 inches (444 x 131 x 635 mm)

Dimensions HxWxD (rack 3U)

5.15 x 17.5 x 25 inches (131 x 444 x 635 mm)

Weight

151 lbs. (68.5 kg)

EX RT CLA module

AC input voltage

156-280 Volts AC

Input frequency

40-70 Hz

Battery charge current

6 A DC

5.6

Heat Rejection

Table 5-4: Full load heat rejection in BTU’s/hr.

System

Operation Mode

On-line

On Battery

5kVA

1327

1944

7kVA

1858

2722

11kVA

2919

4278

5.7

Environmental Characteristics

The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 to +25°C
range and at 5-95% humidity, non-condensing at altitude up to 3280ft without de-rating.

The storage temperature : -20 to 40°C. Humidity : 5-95%, non condensing.

Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at tempera-
tures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers
no longer guarantee operation due to the risk of thermal runaway.

Air enters through the front air vent grills and exits through the back. Always keep air vent grills unobstructed.