Co5: General functions and pre-control circuit

Fb Function

WE

Anl

Comments
Function block parameters

/ Range of values (default setting)

00 Flow sensor

secondary VFsek

ON

All

Co5 -> Fb00 = ON:
In systems Anl 6 and 9 not possible with Co5 -> Fb06 = ON

01 Return flow sensor

primary

ON

Not

6, 9

Co5 -> Fb01 = ON: Return flow limitation active,
Option

steig

Limitation acc. to gradient characteristic

4-pt

Limitation acc. to 4-point characteristic

Note:

Can only be changed after entering key number

02 Reserved

OFF

All

03 4-point

characteristic

OFF 3, 5, 8,

10

Co5 -> Fb03 = ON: 4-point characteristic
Co5 -> Fb03 = OFF: Gradient characteristic
Setting applies for all heating circuits.

04 Delayed

outdoor tempera-
ture adaptation

OFF

All

Co4 -> Fb04 = ON: Option
Ab

When outdoor temperature drops

AufAb When outdoor temperature drops or rises
Function block parameter:
Delay / 1 to 6 °C/h (3 °C/h)

05 Summer

time/winter time
changeover

ON

All

Co4 -> Fb05 = ON:
Automatic summer time/winter time changeover

06 Compensation of

time delays

OFF 1, 2,

4, 7,

10

Co5 -> Fb06 = ON: Only with Co5 -> Fb00 = ON

07 Condensate

accumulation
control

OFF

All

Co5 -> Fb07 = ON: Only with Co5 -> Fb14 = ON
Function block parameter:
Maximum system deviation / 2 to 10 °C (2 °C)

08 Limitation of WMZ OFF

Not

6, 9

Co5 -> Fb08 = ON:
Select limitation, depending on Co9 -> Fb21 to Fb23
---: No limitation
U: Flow rate limitation
P:

Capacity limitation

U-P: Flow rate and capacity limitation
when “U“, “P“ or “U-P“ is selected:
CONST:

Limitation constant

4-Pt:

Limitation acc. to 4-point characteristic,
dependent on outdoor temperature

Note:

Can only be changed after entering key number

EB 5179 EN

101

Appendix