Appendix – Samson Trovis 5100 User Manual

Page 110

Advertising
background image

Display

Parameter designation
Range of values (default settings)

Level of the heating characteristic, return flow

–30 to 30 °C (0 °C)

Characteristic is shifted parallel.

Max. return flow temperature

20 to 90 °C (65 °C)
Only with Co5 -> Fb01 = ON, select: steig

Min. return flow temperature

20 to 90 °C (20 °C)
Only with Co5 -> Fb01 = ON, select: steig

Control according to fixed set point:
Min. return flow temperature = Max. return flow temperature

OT activation value in rated operation

–30 to 50 °C (–15 °C)

The heating continues to run and is not set back outside the
time-of-use when the outdoor temperature is below the OT limit.

OT deactivation value in reduced operation

–10 to 50 °C (10 °C)

The heating is switched off outside the time-of-use when the out-
door temperature is above the OT limit.

110

EB 5179 EN

Appendix