Samson Trovis 5100 User Manual

Page 104

Advertising
background image

Co6: Sensor initialization

Fb Function

WE

Anl

Comments
Function block parameters

/ Range of values (default setting)

00 Sensor selection

general

ON

All

Co6 -> Fb00 = ON: Pt 100; Pt 1000
Co6 -> Fb00 = OFF: Pt 100; PTC

01

to

17

Sensor input 1
to
sensor input 17

OFF

All

Any sensor inputs that are different from the settings for
function block Fb00

Co6 -> Fb01 to Fb17 = ON: select:
Outdoor temperature input:
0/4 to 20 mA, 0 to 10 V = –40 to 50 °C
Other temperature inputs:
0/4 to 20 mA, 0 to 10 V = 0 to 160 °C
Ni200, Ni1000, PTC, NTC, Pt1000, Pt100, 0/4-20, 0-10

23 Sensor calibration

OFF

All

Fb Function block, WE Default setting

Co7: LON communication

Fb Function

WE Anl

Comments
Function block parameters

/ Range of values (default setting)

00 LON active

OFF All Co7 -> Fb00 = ON: LON interface active

01 Controller as

master controller

OFF All Co7 -> Fb01 = ON: Controller is defined as primary controller

(processes the external demand as master controller)
Co7 -> Fb01 = OFF: Controller is defined as secondary

controller

02 Controller time

OFF All Co7 -> Fb02 = ON: Controller time = LON system time

03 Outdoor

temperature 1

OFF All Co7 -> Fb03 = ON: LON outdoor temperature 1

Select:

Terminal number of outdoor sensor

04 Outdoor

temperature 2

OFF All Co7 -> Fb04 = ON: LON outdoor temperature 2

Select:

Terminal number of outdoor sensor

05 Report operational

faults of other LON
participants

OFF All Co7 -> Fb05 = ON: Report fault alarms of other LON

participants

Fb Function block, WE Default setting

104

EB 5179 EN

Appendix