1.6.3 Entering vacation periods

During vacation periods, the controller constantly remains in the reduced operating mode. The
system is monitored for frost. A maximum of 10 vacation periods can be entered.

Parameters

WE

Level / Range of values

Vacation period for heating circuit 1

PA1 / 01.01 to 31.12

Vacation period for heating circuit 2

PA2 / 01.01 to 31.12

Vacation period for heating circuit 3

PA3 / 01.01 to 31.12

Note!
The programmed public holidays and vacations of any heating circuit (HK1, HK2 or HK3) ap-
ply with the setting Co4 -> Fb12 = ON , select 1, 2 or 3 also for the DHW heating.

Proceed as follows:

Switch to configuration and parameter level.
Display: PA1

Select parameter level.

Open parameter level.

Select datapoint for vacation periods.
Display shows:

Open datapoint for vacation periods.
Display shows

: START

If applicable, select – – – –.

Activate editing mode for vacation periods.

blinks.

Set start date of vacation period.

Confirm start date of the vacation period.
Display shows: STOP

Set end of vacation period.

Confirm end of the vacation period.

To enter additional vacation periods, re-select – – – – (between 31.12 and 01.01) and repeat
the steps in the fields highlighted in gray.

Exit the parameter level.

18

EB 5179 EN

Operation