Samson Trovis 5100 User Manual

Page 102

Advertising
background image

Fb Function

WE

Anl

Comments
Function block parameters

/ Range of values (default setting)

09 Pulse input for flow

rate or capacity
limitation

OFF

Not

6, 9

Co5 -> Fb09 = ON: Type of limitation
Option:

U: Flow rate limitation P: Capacity limitation
CONST

Limitation constant

4-Pt:

Limitation acc. to 4-point characteristic

Function block parameter:
Pulse weighting / 0.1 to 10 (10)
Note:

Can only be changed after entering key number

10 Locking manual

levels

OFF

All

Co5 -> Fb10 = ON: Manual intervention not possible and
parameters cannot be changed
Note:

Can only be changed after entering key number

11 Limit monitoring of

a selected sensor
input x

OFF

All

Co5 -> Fb11 = ON: Function block parameters:
Terminal number
Upper/lower limit
Signal edge, binary output
FSr-A/FSr-E: Status alarm to error status register OFF/ON
BA ON/BA OFF: Setting/not setting the binary input
FALL/steig: Negative signal edge/increasing signal edge

12 Limit monitoring of

a selected sensor
input y

OFF

All

Co5 -> Fb12 = ON: Function block parameters:
Terminal number
Upper/lower limit
Signal edge, binary output
FSr-A/FSr-E: Status alarm to error status register OFF/ON
BA ON/BA OFF: Setting/not setting the binary input
FALL/steig: Negative signal edge/increasing signal edge

13 External demand

OFF

Not

3, 5,

8

Co5 -> Fb13 = ON: The highest set point is passed on;
(only with Fb00 = ON possible, in systems Anl 6 and 9
Fb00 = OFF)
Function block parameter:
Boost / 0 to 30 °C (0 °C)
In systems Anl 6 and 9 the demand can only be sent

102

EB 5179 EN

Appendix