Samson Trovis 5100 User Manual

Page 136

Advertising
background image

Parameters

PA5

Range of values

Outdoor temperature, point 3

–30 to 90 °C

Outdoor temperature, point 4

–30 to 90 °C

Return flow temperature, point 1

20 to 90 °C

Return flow temperature, point 2

20 to 90 °C

Return flow temperature, point 3

20 to 90 °C

Return flow temperature, point 4

20 to 90 °C

Max. limit of flow rate, point 1

0 to 99.9 m

3

/h

Max. limit of flow rate, point 2

0 to 99.9 m

3

/h

Max. limit of flow rate, point 3

0 to 99.9 m

3

/h

Max. limit of flow rate, point 4

0 to 99.9 m

3

/h

Max. limit of capacity, point 1

0 to 5999 kW

Max. limit of capacity, point 2

0 to 5999 kW

Max. limit of capacity, point 3

0 to 5999 kW

Max. limit of capacity, point 4

0 to 5999 kW

V-offset of the entire system

–300 to 300 m

3

/h

P-offset of the entire system

–3000 to 3000 kW

Function block parameters Co5

Delay (Fb04 = ON)

1 to 6 °C

Max. system deviation (Fb07 = ON)

2 to 10 °C

Pulse weighting (Fb09 = ON)

0.1 to 10

Boost (Fb13 = ON)

0 to 30 °C

T

Y

(valve transit time) (Fb14 = ON)

15 to 240 s

K

P

(proportional gain) (Fb14/19 = ON)

0.1 to 50

T

N

(reset time) (Fb14/19 = ON)

1 to 999 s

Hysteresis (Fb14 = OFF)

1 to 30 °C

Min. activation time (Fb14 = OFF)

0 to 600 s

Min. deactivation time (Fb14 = OFF)

0 to 600 s

T

V

(derivative-action time) (Fb19 = ON)

0 to 999 s

136

EB 5179 EN

Appendix