Samson Trovis 5100 User Manual

Page 99

Advertising
background image

Fb Function

WE

Anl

Comments
Function block parameters

/ Range of values (default settings)

17 Flow sensor OFF

with room tempera-
ture-dependent
control

OFF

6, 9

Co1, 2, 3 -> Fb17 = ON: Deactivate flow sensor

18 Differential temper-

ature control using
variable weighting
factors

OFF

All

Co1, 2, 3 -> Fb18 = ON: Only for mixer circuits
Function block parameters:
Proportional gain (K

P

) / 0.1 to 999 (0.5)

Reset time (T

N

) / 1 to 999 s (200 s)

Intended temp. difference / 0 to 40 °C (20 °C)
Analog value max. / 0 to 100 % (90 %)
Analog value min. / 0 to 100 % (30 %)

Fb Function block, WE Default setting

Co4: DHW heating

Fb Function

WE

Anl

Comments
Function block parameters

/ Range of values (default setting)

00 Storage tank sensor

SF1

ON

Not

1, 3, 6

Co4 -> Fb00 = OFF, only with storage tank thermostat:
Co4 -> Fb00 = OFF and Co4 -> Fb01 = OFF

01 Storage tank sensor

SF2

ON

Not

1, 3,

6

Co4 -> Fb01 = ON: 2 storage tank sensors SF1 and SF2
Co4 -> Fb01 = OFF: 1 storage tank sensor SF1 or with
Co4 -> Fb00 = OFF: Storage tank thermostat

02 Return flow sensor

DHW circuit

OFF

Not

1, 2,

3, 6

Co4 -> Fb02 = ON: Return flow sensor in DHW circuit active
Function block parameters:
Limitation factor / 0 to 25.5 (1.0)
Note:

Can only be changed after entering the key number

03 Flow sensor

VFS

ON

Not

1, 3,

6

Co4 -> Fb03 = ON: Charging temperature limited with VFT,

regulated with VFS

Co4 -> Fb03 = OFF: Charging temperature regulated with VFT,
without VFS

04 Circulation pump

OFF

Not

1, 3,

6

Co4 -> Fb04 = ON: ZP continues to run during storage tank
charging
Co4 -> Fb04 = OFF: ZP runs acc. to time schedule

05 UP OFF at the start

of reverse control

OFF

5

Co4 -> Fb05 = ON: UP of pump heating circuit is additionally
switched off when reverse control starts.

EB 5179 EN

99

Appendix