Function block parameters Co4

Limitation factor (Fb02 = ON)

0 to 25.5

Activate priority in case of deviation
(Fb06 = ON)

0 to 30 °C

Day of week (Fb08 = ON)

0, 1 to 7

Disinfection temperature (Fb08 = ON)

60 to 90 °C

Boost of charging temperature

0 to 30 °C

Start – Stop (Fb08 = ON)

00:00 to 23:30

T

Y

(valve transit time) (Fb09 = ON)

15 to 240 s

K

P

(proportional gain) (Fb09/14 = ON)

0.1 to 50

T

N

(reset time) (Fb09/14 = ON)

1 to 999 s

T

V

(derivative-action time) (Fb14 = ON)

0 to 999 s

Data for heating circuits (Fb12 = ON)

1 to 3

Max. system deviation (Fb13 = ON)

2 to 10 °C

PA5: System-wide parameters

Parameters

PA5

Range of values

Gradient, return flow

0.4 to 3.2

Level, return flow

–30 to 30 °C

Maximum return flow temperature

20 to 90 °C

Minimum return flow temperature

20 to 90 °C

Maximum capacity of entire system

0.1 to 5999 kW

Maximum capacity of heating

0.1 to 5999 kW

Maximum capacity of DHW heating

0.1 to 5999 kW

Proport.-action coefficient for limitation

0.1 to 10

Maximum flow rate of entire system

0.01 to 99.9 m

3

/h

Maximum flow rate of heating

0.01 to 99.9 m

3

/h

Maximum flow rate of DHW heating

0.01 to 99.9 m

3

/h

Minimum flow rate

0.01 to 99.9 m

3

/h

Proport.-action coefficient for limitation

0.1 to 10

Outdoor temperature, point 1

–30 to 90 °C

Outdoor temperature, point 2

–30 to 90 °C

EB 5179 EN

135