Co8: Error initialization

Fb Function

WE

Anl

Comments
Function block parameters

/ Range of values (default setting)

00 Dial-up also upon

corrected fault

OFF

All

CO8 -> Fb00 = ON: Dial-up to the building control station
both when a fault was detected and a fault was corrected
CO8 -> Fb00 = OFF: Dial-up to building control station only
when fault was detected

01

to

17

BE1 in FSr
to
BE 17 in FSr

OFF

All

Co8 -> Fb01 to Fb17 = ON:
Option:

Rising signal edge/make contact
Negative signal edge/break contact

Note:

Can only be changed after entering key number

22 Limit monitoring

OFF

All

Configurable over Modbus

23 Alarm binary input

changed

OFF

All

Co8 -> Fb23 = ON: Subsequent faults reported in error status
register (bit D11)

Fb Function block, WE Default setting

Co9: Modbus and meter bus communication

FB Function

WE

Comments
Function block parameters

/ Range of values (default setting)

00 Modbus

ON CO9 -> FB00 = ON: Modbus active

01 Modem

OFF CO9 -> FB01 = ON: Modem active

02 Modem dialing

mode

OFF CO9 -> FB02 = ON: Pulse dialing

CO9 -> FB02 = OFF: Tone dialing

03 Lock dial-up

OFF CO9 -> FB03 = ON: No dial-up in case of fault

04 Modbus 16-bit

addressing

OFF CO9 -> Fb04 = ON: 16-bit addressing

CO9 -> Fb04 = OFF: 8-bit addressing

05 Reserved

06 Text message alarm OFF CO9 -> FB06 = ON: Fault alarm sent to mobile phone

07 Text message

dialing mode

OFF CO9 -> FB07 = ON: Pulse dialing

CO9 -> FB07 = OFF: Tone dialing

10 Fax alarm

OFF CO9 -> FB10 = ON: Alarm sent to fax

11 Fax dialing mode

OFF CO9 -> FB11 = ON: Pulse dialing

CO9 -> FB11 = OFF: Tone dialing

EB 5179 EN

105