Appendix – Samson Trovis 5100 User Manual

Page 108

Advertising
background image

Display

Parameter designation
Range of values (default settings)

4-point characteristic
Point 1: Flow temperature
Flow temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.

20 to 130 °C
(point 1 = 70 °C, point 2 = 55 °C, point 3 = 40 °C, point 4 = 25 °C)

4-point characteristic
Point 1: Return flow temperature
Return flow temperatures of the points 2, 3, 4 are marked by
squares below the numbers 2, 3, 4.

20 to 90 °C
(point 1 = 65 °C, point 2 = 50 °C, point 3 = 35 °C, point 4 = 20 °C)

4-point characteristic Set-back difference

Varying set-back differences can be entered for the second and
third points. The corresponding point is marked by squares below
the numbers 2 and 3.

0 to 50 °C (20 °C)

Maximum flow temperature

20 to 130 °C (90 °C)

Minimum flow temperature

20 to 130 °C (20 °C)

Control according to fixed set point:
Min. return flow temperature = Max. return flow temperature

108

EB 5179 EN

Appendix

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

˚C

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

˚C

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Advertising
This manual is related to the following products: