Fb Function

WE

Anl

Comments
Function block parameters

/ Range of values (default settings)

09 RK switched off

when switch at
MAN-CLOSED

OFF

All

Co1, 2, 3 -> Fb09 = ON: UP still runs until 1 x T

Y

.

The flow sensor is no longer be read.

10 4-point character-

istic

OFF

Not

3, 5,

8, 10

Co1, 2, 3 -> Fb10 = ON: 4-point characteristic
Co1, 2, 3 -> Fb10 = OFF: Gradient characteristic

11 Summer mode

ON

All

Co1, 2, 3 -> Fb11 = ON: Function block parameters:
Start summer mode / 01.01 to 31.12 (01.05)
End summer mode/ 01.01 to 31.12 (30.09)
Outdoor temp. limit for summer mode / 0 to 30 °C (18 °C)

12 Potentiometer input

Release HK

OFF

All

Co1, 2, 3 -> Fb12 = ON: Valve position feedback
(0 to 1000

Ω

), 1000

Ω

additional resistor required

Co1, 2, 3 -> Fb12 = OFF: RK released with binary signal;
Option

FrG-E: Released over bin. signal (potentiometer)
FrG-A: Released over time schedule

With FrG-A:RLG:

Configuration acc. to input

FREE:

Input freely available

13 Pump

management

OFF

All

Co1, 2 -> Fb13 = ON: BA 2, 4 OFF outside time-of-use
Co1, 2 -> Fb13 = OFF: BA 2, 4 ON outside time-of-use

14 Continuous-action

control for heating
circuit

OFF

All

Co1, 2, 3 -> Fb14 = ON: Continuous-action control 0 to 10 V
Function block parameters:
K

P

(proportional gain) / 0.1 to 50.0 (0.5)

T

N

(reset time) / 1 to 999 s (200 s)

T

V

(derivative-action time) / 0 to 999 s (0 s)

15 Three-step control

for heating circuit

ON

All

Co1, 2, 3 -> Fb15 = ON: Three-step control;
Function block parameters:
K

P

(proportional gain) / 0.1 to 50.0 (0.5)

T

N

(reset time) / 1 to 999 s (200 s)

T

Y

(valve transit time) / 15 to 240 s (120 s)

UP lag time / 120 to 1200 s (240 s)
Co1, 2, 3 -> Fb15 = OFF: On/off control
Function block parameters:
Hysteresis / 1 to 30 °C (5 °C)
Min. activation time / 0 to 600 s (120 s)
Min. deactivation time / 0 to 600 s (120 s)
UP lag time / 120 to 1200 s (240 s)

16 Parameter

optimization

OFF

6, 9

Co1, 2, 3 -> Fb16 = ON: Automatic parameter optimization
(K

P

, T

N

, T

V

)

98

EB 5179 EN

Appendix