Pa4: dhw heating, Appendix – Samson Trovis 5100 User Manual

Page 112

Advertising
background image

Display

Parameter designation
Range of values (default settings)

Copy times-of-use of HK2 for HK3

Only in systems Anl 3, 6

PA4: DHW heating

Display

Parameter designation
Range of values (default settings)

DHW demand ON

20 to 90 °C (40 °C)

Systems with a storage sensor SF1
Co4 -> Fb02 = ON , Fb02 = OFF

Hysteresis

0 to 30 °C (5 °C)

DHW demand ON

20 to 90 °C (40 °C)

Systems with two storage sensors SF1 and SF2
Co4 -> Fb02 = ON , Fb02 = ON

112

EB 5179 EN