background image

PA1 to PA3: Heating circuits HK1 to HK3

Parameters

PA1

PA2

PA3

Range of values

Gradient, flow

0.4 to 3.2

Level, flow

–30 to 30 °C

Maximum flow temperature

20 to 130 °C

Minimum flow temperature

20 to 130 °C

Set-back difference

0 to 50 °C

Gradient, return flow

0.4 to 3.2

Level, return flow

–30 to 30 °C

Outdoor temperature; point 1

–30 to 90 °C

Outdoor temperature; point 2

–30 to 90 °C

Outdoor temperature; point 3

–30 to 90 °C

Outdoor temperature; point 4

–30 to 90 °C

Flow temperature; point 1

20 to 130 °C

Flow temperature; point 2

20 to 130 °C

Flow temperature; point 3

20 to 130 °C

Flow temperature; point 4

20 to 130 °C

Return flow temperature; point 1

20 to 90 °C

Return flow temperature; point 2

20 to 90 °C

Return flow temperature; point 3

20 to 90 °C

Return flow temperature; point 4

20 to 90 °C

Set-back temperature; point 2

0 to 50 °C

Set-back temperature; point 3

0 to 50 °C

Day set point

10 to 90 °C

Night set point

10 to 90 °C

Sustained temperature

10 to 90 °C

Maximum return flow temperature

20 to 90 °C

Minimum return flow temperature

20 to 90 °C

OT activation value rated operation

–30 to 50 °C

OT deactivation value
reduced operation

–10 to 50 °C

OT deactivation value
rated operation

0 to 90 °C

EB 5179 EN