Parameters

PA1

PA2

PA3

Range of values

Times-of-use

Monday

Start – Stop (1)

00:00 to 24:00 h

Monday

Start – Stop (2)

00:00 to 24:00 h

Tuesday

Start – Stop (1)

00:00 to 24:00 h

Tuesday

Start – Stop (2)

00:00 to 24:00 h

Wednesday Start – Stop (1)

00:00 to 24:00 h

Wednesday Start – Stop (2)

00:00 to 24:00 h

Thursday

Start – Stop (1)

00:00 to 24:00 h

Thursday

Start – Stop (2)

00:00 to 24:00 h

Friday

Start – Stop (1)

00:00 to 24:00 h

Friday

Start – Stop (2)

00:00 to 24:00 h

Saturday

Start – Stop (1)

00:00 to 24:00 h

Saturday

Start – Stop (2)

00:00 to 24:00 h

Sunday

Start – Stop (1)

00:00 to 24:00 h

Sunday

Start – Stop (2)

00:00 to 24:00 h

Function block parameters Co1, Co2, Co3

Limitation factor (Fb01 = ON)

0 to 25.5

Advance heating time (Fb05 = ON)

0 to 360 min

Start summer mode (Fb11 = ON)

01.01 to 31.12

Stop summer mode (Fb11 = ON)

01.01 to 31.12

Outdoor temp. limit in summer mode
(Fb11 = ON)

0 to 30 °C

K

P

(proportional gain) (Fb14/15 = ON)

0.1 to 50

T

N

(reset time) (Fb14/15 = ON)

1 to 999 s

T

V

(derivative-action time) (Fb14 = ON)

0 to 999 s

T

Y

(valve transit time) (Fb15 = ON)

15 to 240 s

UP lag time (Fb15 = ON/OFF)

120 to 1200 s

Hysteresis (Fb15 = OFF)

1 to 30 °C

Min. activation time (Fb15 = OFF)

0 to 600 s

Min. deactivation time (Fb15 = OFF)

0 to 600 s

Proportional gain (K

P

) (Fb18 = ON)

0.1 to 999

Reset time (T

N

) (Fb18 = ON)

1 to 999 s

132

EB 5179 EN

Appendix