12.2 Parameter list

PA1 to PA3: Heating circuits HK1 to HK3

Display

Parameter designation
Range of values (default settings)

Gradient of the heating characteristic, flow

0.4 to 3.2 (1.8)

Level of the heating characteristic, flow

–30 to 30 °C (0 °C)

4-point characteristic

Press key to adjust the following parameters:
outdoor temperature,
flow temperature,
return flow temperature and
set-back difference.

4-point characteristic
Point 1: Outdoor temperature
Outdoor temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.

–30 to 90 °C
(point 1 = –15 °C, point 2 = –5 °C, point 3 = 5 °C, point 4 = 15 °C)

EB 5179 EN