1.6.2 Entering public holidays

On public holidays, the times-of-use specified for Sunday apply. A maximum of 20 public holi-
days may be entered.

Parameters

WE

Level / Range of values

Public holidays f. heating circuit 1

PA1 / 01.01 to 31.12

Public holidays f. heating circuit 2

PA2 / 01.01 to 31.12

Public holidays f. heating circuit 3

PA3 / 01.01 to 31.12

Note!
The programmed public holidays and vacations of any heating circuit (HK1, HK2 or HK3) ap-
ply with the setting Co4 -> Fb12 = ON , select 1, 2 or 3 also for the DHW heating.

Proceed as follows:

Switch to configuration and parameter level.
Display: PA1

Select parameter level.

Open parameter level.

Select datapoint for public holidays.
Display shows:

Open data point for public holidays.

If applicable, select – – – –.

Activate editing mode for public holiday.

blinks.

Edit public holiday

Confirm public holiday.

To enter additional public holidays, re-select – – – – (between 31.12 and 01.01) and repeat the
steps in the fields highlighted in gray.

Exit the parameter level.

Return to the operating level.

16

EB 5179 EN

Operation

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24