3 fixed set point con trol 41, Fixed set point control – Samson Trovis 5100 User Manual

Page 41

Advertising
background image

The

Max. flow temperature and Min. flow temperature parameters mark the upper and lower lim-

its of the flow temperature.

Functions

WE

Configuration

4-point characteristic

OFF

Co1, 2, 3 -> Fb10 = ON

4-point characteristic

OFF

Co4 -> Fb03 = ON (Anl 3, 5, 8 and 10)

Parameters

WE

Parameter level / Range of values

Flow temperature

Point 1
Point 2
Point 3
Point 4

70 °C
55 °C
40 °C
25 °C

PA1, 2, 3 / 20 to 130 °C

Outdoor temperature

Point 1
Point 2
Point 3
Point 4

–15°C
– 5 °C

5 °C

15 °C

PA1, 2, 3 / –30 to 90 °C

Return flow temperature Point 1

Point 2
Point 3
Point 4

65 °C
50 °C
35 °C
20 °C

PA1, 2, 3 / 20 to 90 °C

Set-back difference

Points 2, 3

20 °C PA1, 2, 3 / 0 to 50 °C

Max. flow temperature

90 °C PA1, 2, 3 / 20 to 130 °C

Min. flow temperature

20 °C PA1, 2, 3 / 20 to 130 °C

EB 5179 EN

41

Functions of the heating circuit

t

VLmax

t

VLmin

t

VL

100

90

80

70

60

50

40

30

20

10

[˚C]

20

15

10

5

0

–5

–10 –15 –20

P1

P2

P3

P4

[˚C]

t

A

Fig. 3 · 4-point characteristic

P1 to 4 Points 1 to 4
tVL

Flow temperature

tA

Outdoor temperature

...min

Minimum tVL

...max

Maximum tVL
4-point characteristic
Reduced 4-point
characteristic