14 relea sing the hea ting cir cuit 50, 15 posi tion feed back in pre-con trol cir cuit 50, Pump ma na ge ment 50 – Samson Trovis 5100 User Manual

Page 50: Releasing the heating circuit, Position feedback in pre-control circuit, 13 pump management

Advertising
background image

Functions

WE

Configuration

Room sensor RF1, 2, 3

OFF

Co1, 2, 3 -> Fb00 = ON

Room temperature dependent control

OFF

Co1, 2, 3 -> Fb06 = ON

Parameter optimization

OFF

Co1, 2, 3 -> Fb16

Flow sensor OFF when room temperature
dependent control is used

OFF

Co1, 2, 3 -> Fb17

5.13 Pump management

To control the circulation pumps for the heating circuits (UP1 and UP2), reed relay outputs can
be used instead of the relay output. Depending on the operating state, the circulation pumps run
during the times-of-use regulated depending on the differential pressure. The differential pres-
sure is regulated by the pumps. Outside the times-of-use the circulation pumps are switched
back to the minimum speed. The binary outputs BA1 to BA4 have the following function:

4

BA1, BA3: Circulation pump on and off

4

BA2, BA4: Reduce pump speed

If the circulation pump is to be switched on, the contact of BA1 or BA3 is closed. The binary out-
puts BA2 and BA4 can be configured over the function blocks Co1, 2 -> Fb13.

4

Co1, 2 -> Fb13 = ON:

BA2, BA4 = OFF outside the time-of-use

4

Co1, 2 -> Fb13 = OFF:

BA2, BA4 = ON outside the time-of-use

Function

WE

Configuration

Pump management

OFF

Co1, 2 -> Fb13

Note!
Refer to the pump manufacturer instructions for the exact terminal assignments of pumps since
the terminal assignments vary depending on the pump.
In systems Anl 3, 5, 8 and 10, the pumps of an uncontrolled heating circuit can be switched on
and off over an external binary signal. For this purpose, deactivate the Potentiometer input
function (Co1 to Co3 -> Fb12 = OFF) and select the function block parameter FrG-E.