In the sto ra ge tank char ging sys tem 54, 2 dhw heating in the storage tank system – Samson Trovis 5100 User Manual

Page 54

Advertising
background image

Parameters

WE

Parameter level / Range of values

DHW demand ON

40 °C

PA4 / 20 to 90 °C

DHW demand OFF

45 °C

PA4 / 20 to 90 °C

Charging temperature

55 °C

PA4 / 20 to 90 °C

Heat exchanger charging pump
deactivation limit

50 °C

PA4 / 20 to 90 °C

Storage tank charging pump
deactivation limit

50 °C

PA4 / 20 to 90 °C

Maximum charging temperature

120 °C PA4 / 20 to 120 °C

6.2 DHW heating in the storage tank system

Start storage tank charging

The controller can be reconfigured for all systems with DHW heating to control a DHW storage
tank with heating register (storage tank system).

The controller switches the storage tank charging pump (SLP) on and off and controls the mixing
valve for the DHW circuit. A mixing valve in the DHW circuit does not exist in system Anl 2. The
sensor VFS is connected to terminal 28 and the storage tank charging pump to terminal 45.

The controller starts the storage tank charging when the water temperature measured at sensor
SF1 falls below the

DHW demand ON by 0.1 °C. If the flow temperature in the system is higher

than the required charging temperature, the controller attempts to reduce it in the heating circuit
for maximum three minutes before the storage tank charging pump starts to run.

54

EB 5179 EN

Appendix

VL

RL

SLP VFS

ZP

KW

Zirk.

TW

SF1

Fig. 6 · DHW heating in storage tank system, applies to systems Anl 4, 5, 7, 8, 9 and 10

Anl 2: without three-way valve

SLP

Storage tank charging
pump

SF1

Storage sensor 1

VFS

Flow sensor

ZP

Circulation pump

KW

Cold water

TW

Domestic hot water (DHW)

VL

Flow

RL

Return flow