3 prio rity ope ra tion 55, 1 reverse con trol 55, Priority operation – Samson Trovis 5100 User Manual

Page 55: Reverse control

Advertising
background image

When there is no heating operation or when the flow temperature in the system is lower, the
storage tank charging pump is switched on immediately.
If a storage tank thermostat is used, the storage tank charging pump is switched on when the
temperature T =

Charging temperature – 5 °C is reached at sensor VFS.

Note!
The charging temperature VFS is controlled in system Anl 2 by the primary valve. In all the other
systems (Anl 4, 5, 7, 8, 9 and 10) the mixing valve regulates the charging temperature VFS.

When the Circulations pump function is active, the circulation pump remains in operation ac-
cording to the time schedule. The pumps is switched off when this function is deactivated.

The Mixing valve always active function allows the heat exchanger to maintain the charging
temperature using the mixing valve. The heat exchanger charging pump remains switched on
and the return flow temperature is not limited outside the times-of-use.

Stop storage tank charging

The controller stops charging the storage tank when the water temperature in the storage tank
measured at sensor SF1 exceeds the temperature T =

Charging temperature + Hysteresis by

0.1 °C. When there is no heating operation or when the flow temperature demand in the system
is lower, the corresponding valve is closed.

The storage tank charging pump is switched off when the charging temperature at sensor VFS
has fallen below the

Storage tank charging pump deactivation limit; however, at the latest, af-

ter t

= 2 x Transit time of the primary valve.

In the default setting, the storage tank is charged by 5 °C to at least 50 °C when the storage tank
temperature falls below 40 °C. The charging temperature is 55 °C. On completing the storage
tank charging, the heating valve is closed and the charging pump continues to run until the
charging temperature falls below 50 °C.

Functions

WE

Configuration

Storage sensor SF1

ON

Co4 -> Fb00 = ON

Storage tank system

OFF

Co4 -> Fb10 = ON

Circulation pump

OFF

Co4 -> Fb04

Mixing valve always active

OFF

Co4 -> Fb11

EB 5179 EN

55