5 con den sate accu mu la tion con trol 60, 6 com pen sa ting for time delays 60, Condensate accumulation control – Samson Trovis 5100 User Manual

Page 60: Compensating for time delays

Advertising
background image

Function

WE

Configuration

Return flow sensor RüF1, 2, 3

OFF
1.0

Co1, 2, 3 -> Fb01 = ON
Limitation factor / 0 to 25.5

Parameters

WE

Parameter level / Range of values

Max. return flow temperature

65 °C

PA1, 2, 3 / 20 to 90 °C

Min. return flow temperature

20 °C

PA1, 2, 3 / 20 to 90 °C

In systems with a DHW in a secondary circuit, the control during DHW heating uses the

Return

flow limitation temperature for DHW parameter (systems Anl 2, 4, 5 and 10). In the transition
time or in summer mode, the heating circuit can be operated with a lower return flow tempera-
ture while at the same time performing proper storage tank charging.

The

Return flow limitation temperature for DHW parameter can also be active in systems Anl 4,

5, 7, 8, 9 and 10 at a separate return flow sensor. The separate sensor RüFTW (return flow sen-
sor for DHW) must in this case be installed in the return flow of the DHW circuit.

Note!
In system Anl 2 , the sensor RüFprim is installed in the return flow of the primary circuit. In this
case, the Return flow sensor, primary function must be activated (Co5 -> Fb01 = ON).

Function

WE

Configuration

Return flow sensor in DHW circuit

OFF
1.0

Co4 -> Fb02 = ON
Limitation factor / 0 to 25.5

Parameter

WE

Parameter level / Range of values

Return flow limitation temperature for DHW

45 °C

PA4 / 20 to 90 °C

Note!
To ensure that the preset return flow temperature limit can be met, make sure that
– the heating characteristic is not adjusted to ascend too steeply,
– the speed of the circulation pumps is not set too high,
– the heating systems have been calibrated.

60

EB 5179 EN

System-wide functions