7.7 Three-step control

The flow temperature can be controlled using a PI algorithm. The valve reacts to pulses that the
controller emits when a system deviation occurs. The length of the first pulse, in particular, de-
pends on the extent of the system deviation and the selected

Proportional gain K

P

(the pulse

length increases as K

P

increases). The pulse and pause lengths change continuously until the

system deviation has been eliminated. The pause length between the single pulses is greatly in-
fluenced by the

Reset time T

N

(the pause length increases as T

N

increases).

The

Transit time T

Y

specifies the time required by the valve to travel through the range of 0 to

100 %.

The three-step control can be configured separately for individual heating circuits, for the DHW
heating and for the pre-control circuit.

Functions

WE

Configuration

Three-step control
for heating circuit

ON
0.5
200 s
120 s
240 s

Co1, 2, 3 -> Fb15 = ON
K

P

(proportional gain) / 0.1 to 50.0

T

N

(reset time) / 1 to 999 s

T

Y

(transit time) / 15, 30, …, 240 s

UP lag time / 120 to 1200 s

Three-step control
for DHW heating

ON
0.5
200 s
120 s

Co4 -> Fb09 = ON
K

P

(proportional gain) / 0.1 to 50.0

T

N

(reset time) / 1 to 999 s

T

Y

(transit time) / 15, 30, …, 120 s

Three-step control
for pre-control circuit

ON
0.5
200 s
120 s

Co5 -> Fb14 = ON
K

P

(proportional gain) / 0.1 to 50.0

T

N

(reset time) / 1 to 999 s

T

Y

(transit time) / 15, 30, …, 240 s

No further pulses are issued at the three-step outputs when the control signal deactivation func-
tion is activated when the total of the timing pulses (uninterrupted in one direction) is larger than
three times the control valve transit time T

Y

. In this case, it can be assumed that the control valve

is either completely open or completely closed; other signals do not cause any changes in the
control valve.

Function

WE

Configuration

Control signal deactivation

OFF

Co5 -> Fb18 = ON

62

EB 5179 EN

System-wide functions