A heat meter with pulse output connected at input V

max

(terminal 30) can be used either to limit

the system flow rate (parameter code: U) or the system capacity (parameter code: P). The pulse
weighting of the heat meter (WMZ) and the type of limitation selected must be entered. The dis-
played value corresponds to the unit l/pulse or kWh/pulse.
When the pulse rate reaches the current maximum limit, the flow set point of the control circuit
RK1 is reduced. How strongly the controller responds is determined by the

Proportional-action

coefficient for limitation.

Example to determine the limit value:
If a capacity of 30 kW is to be limited, the following limit value must be set for a heat meter with
an output of one pulse per kilowatt-hour:

P

30 kW

1 KWh / pulse

30 pulse / h

=

=

Settings for capacity limitation

Functions

WE

Configuration

Limitation of heat meter (WMZ)

OFF

Co5 -> Fb08 = OFF

Pulse input for flow rate or capacity limitation

OFF

10

Co5 -> Fb09 = ON, select: P
CONST:

Limitation constant

4-Pt:

Limitation acc. to
4-point characteristic

Pulse weighting / 0.1 to 10

Parameters

WE

Parameter level / Range of values

Maximum capacity of the entire system

50 kW

PA5 / 0.1 to 5999 kW

Maximum capacity of the DHW heating

50 kW

PA5 / 0.1 to 5999 kW

Proportional-action coefficient for the limitation

1.0

PA5 / 0.1 to 10

Select

CONST additionally for:

Maximum capacity of the heating

50 kW

PA5 / 0.1 to 5999 kW

Select

4-Pt additionally for:

Outdoor temperature Point 1

Point 2
Point 3
Point 4

–15 °C
– 5 °C

5 °C

15 °C

PA5 /–30 to 90 °C

Maximum capacity limitation, points 1 to 4

50 kW

PA5 / 0.1 to 5999 kW

EB 5179 EN

65

System-wide functions