Rs-485 78 – Samson Trovis 5100 User Manual

Page 78

Advertising
background image

Functions

WE

Configuration

Modem

OFF

Co9 -> Fb01 = ON

Modem dialing procedure

OFF

Co9 -> Fb02

Lock dial-up

OFF

Co9 -> Fb03

Dial-up also upon corrected fault

OFF

Co8 -> Fb00

Parameters

*

WE

Parameter level / Range of values

Station address (ST.-NR)

255

PA9 / 1 to 247

(1 to 999 with Co9 -> Fb04 = ON)

Baud rate (BAUD)

9600

PA9 / 300 to 19200

Cyclic initialization (I)

30 min PA9 / 0 to 255 min

Modem dial interval between calls (P)

5 min

PA9 / 1 to 255 min

Modem timeout (t)

5 min

PA9 / 1 to 255 min

Number of redial attempts (C)

5

PA9 / 0 to 99

Phone number of building control station
(tELno)

PA9 / Configurable as required**

Phone number of alternative recipient
(rESno)

PA9 / Configurable as required**

** Digits 0 to 9, P = Pause, - = End, max. 22 characters

* –> Section 9.3 (“Description of communication parameters to be adjusted“)

9.2 RS-232/RS-485 system bus interface (for four-wire bus) in combina-

tion with cable converters

A constant bus connection is required (data cable) for operation of the district heating controller
in conjunction with cable converters. The bus line is routed to the individual control instruments
in an open ring. At the end of the bus line, the data cable is connected to the control station us-
ing an RS-485/RS-232 converter (e.g. TROVIS 5484). The maximum range of the bus connec-
tion (cable length) is 1,200 meters. A maximum of 32 devices can be connected to such a seg-
ment. If you wish to use more than 32 devices in line or need to bridge greater distances, make
sure repeaters (e.g. TROVIS 5482) are installed to replicate the signal. With 8-bit addressing, a
maximum of 246 devices can be addressed and connected to a bus.

Warning!

You are required to follow the relevant standards and regulations concerning lightning and
overvoltage protection on installation.

78

EB 5179 EN