5 lon com mu ni ca tion 83, Lon communication – Samson Trovis 5100 User Manual

Page 83

Advertising
background image

4

A system with simultaneous room heating and DHW heating requires maximum energy.

4

A system with a fully charged storage tank which performs only room heating requires less
energy.

4

A system which suspends room heating during DHW heating requires less energy.

As a result, three different maximum limit values can be specified:

4

Max. limit value to determine the absolute upper limit

4

Max. limit value for heating for exclusive operation of the room heating

4

Max. limit value for DHW for exclusive operation of the DHW heating

In all systems without DHW heating or without heating circuit, only the

Max. limit value for the

flow rate or capacity can be set.

Capacity limitation

Parameters

WE

Parameter level / Range of values

Maximum capacity of the entire system

50 kW

PA5 / 0.1 to 5999 kW

Maximum capacity of the DHW heating

50 kW

PA5 / 0.1 to 5999 kW

Proportional-action coefficient for limitation

1.0

PA5 / 0.1 to 10

By selecting “CONST“ additionally

Maximum capacity of the heating

50 kW

PA5 / 0.1 to 5999 kW

By selecting “4-Pt“ additionally

Outdoor temperature Point 1

Point 2
Point 3
Point 4

–15 °C
– 5 °C

5 °C

15 °C

PA5 /–30 to 90 °C

Maximum limit of capacity, points 1 to 4

50 kW

PA5 / 0.1 to 5999 kW

Flow rate capacity

Parameters

WE

Parameter level / Range of values

Maximum flow rate of the entire system

9 m

3

/h

PA5 / 0.01 to 99.9 m

3

/h

Maximum flow rate of the DHW heating

9 m

3

/h

PA5 / 0.01 to 99.9 m

3

/h

Proportional-action coefficient for limitation

1.0

PA5 / 0.1 to 10

By selecting “CONST“ additionally

Maximum flow rate of the heating

9 m

3

/h

PA5 / 0.01 to 99.9 m

3

/h

By selecting “4-Pt“ additionally

EB 5179 EN

83

Communication