Ac tua tor 91, Pump 91, Sen sor 91 – Samson Trovis 5100 User Manual

Page 91

Advertising
background image

Connecting the sensors

Cables with a minimum cross-section of 2 x 0.5 mm² can be connected to the terminals at the
back panel of the housing.

Connecting the actuators

Connect cables with at least 1.5 mm² suitable for damp locations to the terminals of the control-
ler output. The direction of travel needs to be checked at start-up.

4

Set mode switch to (+). Valves must open.

4

Set slide switch to (–). Valves must close.

Connecting the pumps

Connect all cables with at least 1.5 mm² to the terminals of the controller as illustrated in the corre-
sponding connection diagram (–> page 92 to 96).

Wiring plan legend (page 92 to 96):

AA Analog output 0 to 10 V

VFS Flow sensor in storage tank

AE

Analog input 0 to 10 V

VFT Flow sensor in heat exchanger

BA

Binary output

GND Ground

BA1 UP HK1 ON/OFF

GWx Limit alarm to terminal x

BA2 UP HK1 Speed reduced

GWy Limit alarm to terminal y

BA3 UP HK2 ON/OFF

ZB

Meter bus

BA4 UP HK2 Speed reduced

HK

Heating circuit

BE/V Binary input for flow rate

FW District heating circuit

AF

Outdoor sensor

TW DHW circuit

FG

Potentiometer (terminal 3 at Type 5244)

SLP Storage tank charging pump

RF

Room sensor (terminal 1 at Type 5244)

TLP

Heat exchanger charging pump

RüF Return flow sensor

UP

Circulation pump

SF

Storage tank sensor
(1: Storage tank ON; 2: Storage tank OFF)

ZP

Circulation pump

STh Storage tank thermostat

Option Type 5244 or 5257-5

(Terminal base of room panel is illustrated)

VF

Flow sensor

EB 5179 EN

91