Appendix

12.1 Function block lists

Co1 to Co3: Heating circuit 1 to 3

Fb Function

WE

Anl

Comments
Function block parameters

/ Range of values (default settings)

00 Room sensor

RF1, 2, 3

OFF

All

Co1, 2, 3 -> Fb00 = ON: Room sensor active
In systems Anl 3, 5 and 8 only for optimization and display

01 Return flow sensor

RüF1, 2, 3

OFF

All

Co1, 2, 3 -> Fb01 = ON: Return flow sensor active
Function block parameters:
Limitation factor / 0 to 25.5 (1.0)
In system Anl 6 only after entering key number.

02 Outdoor sensor

AF1, 2, 3
*

HK1 = ON
HK2 = OFF
HK3 = OFF

*

All

Co1, 2, 3 -> Fb02 = ON: Outdoor sensor active;
Option:

Sensor
Lon1
Lon2

In HK1 it can only be deactivated when all heating circuits are
configured as room temperature-dependent control. The out-
door temperature is then set to the fictive value of 3 °C.

03 Reserved

04 Reserved

05 Optimization

OFF

All

Co1, 2, 3 -> Fb05 = ON:
Option:

1

Activation according to outdoor temperature;
set-back acc. to time schedule*

2

Activation according to outdoor temperature;
set-back acc. to room sensor*

3

Activation and deactivation acc. to room sensor

* Function block parameters:
Advance heating time / 0 to 360 min (120 min)
Option 2 and 3 only with Co1, 2, 3 -> Fb00 = ON

06 Room temperature-

dependent control

OFF

6, 9

Co1, 2, 3 -> Fb06 = ON: Room temperature-dependent con-
trol active

07 Adaptation

OFF

Not

3, 5, 8

Co1, 2, 3 -> Fb07 = ON: Adaptation active; only with
Co1, 2, 3 -> Fb00 = ON and Co1, 2, 3 -> Fb10 = OFF

08 Flash adaptation

OFF Not 3,

5, 8

Co1, 2, 3 -> Fb08 = ON: Flash adaptation active;
only with Co1, 2, 3 -> Fb00 = ON

EB 5179 EN

97

Appendix