Siemens SIPART PS2 6DR52xx User Manual

Page 100

Advertising
background image

Operation

100

SIPART PS2 Manual

A5E00074631--06

Automatic initialization (see chapter 3.6, page 72)

By selecting “Strt” and pressing the increment key

for at least

5 seconds, automatic initialization is started. The initialization process

is displayed by “RUN 1” to “RUN 5” (see figure 3-35, page 83 to

figure 3-38, page 86).

Manual initialization

By selecting “Strt” and pressing the increment key

for at least

5 seconds, manual initialization is started. The manual initialization

process is described in chapter 3.6.3, page 76 and chapter 3.6.6,

page 81.

.

NOTE
If the positioner has already been initialized, for INITA and INITM it is

possible to transfer it to its non-initialized state without changing the

remaining parameters by pressing the decrement key

for 5 s.

Current range of the setpoint
The selection of the current range depends on the connection type.

“0mA” (0 to 20 mA) is only possible in three-/four-wire connections (see

figure 3-23, page 64).

Setpoint direction (see figure 4-8, page 101)
The setting of the setpoint direction serves to reverse the direction of

action of the setpoint. It is used mainly for the split range mode and in

single-acting actuators with the safety position “up”.

Split range start (see figure 4-8)

and

Split range end (see figure 4-8)
The parameters “8.SPRA” and “9.SPRE” in connection with the

parameter “7.SDIR” serve to restrict the active setpoint range. In this

way split range tasks can be solved with the following characteristics.

S

rising / falling

S

falling / rising

S

falling / falling

S

rising / rising

4.INITA

5.INITM

6.SCUR

7.SDIR

8.SPRA

9.SPRE

Advertising
This manual is related to the following products: