Siemens SIPART PS2 6DR52xx User Manual

Page 118

Advertising
background image

Operation

118

SIPART PS2 Manual

A5E00074631--06

Monitoring of the upper temperature limit
The current temperature in the positioner housing is measured by a

sensor on the electronic circuit board. This parameter is for the

three-level monitoring of the upper temperature limit.

Temperature unit
The temperature unit can be switched over by pressing the Greater

Than or Smaller Than button between °C and °F. Another way of

switching over is the H1.TUNIT parameter for monitoring the lower

temperature limit. The selected unit applies to all temperature-related

parameters.

Threshold 1
First threshold for monitoring the upper temperature limit. The factory

setting is 75.0°C. If the temperature exceeds the set value, the thres-

hold 1 error message is triggered.

Threshold 2
Second threshold for monitoring the upper temperature limit. The

factory setting is 80.0°C. If the temperature exceeds the set value,

the threshold 2 error message is triggered.

Threshold 3
Third threshold for monitoring the upper temperature limit. The factory

setting is 90.0°C. If the temperature exceeds the set value, the thres-

hold 3 error message is triggered.

J. TMAX

J1.TUNIT

J2.LEVL1

J3.LEVL2

J4.LEVL3