Preparing for Operation

75

SIPART PS2 Manual

A5E00074631--06

5. Start initialization by pressing the key

for longer than 5 s.

Display:

During the initialization phase “RUN1” to “RUN5” appear one after

another in the bottom display (see also structograms figure 3-35,

page 83 to figure 3-38, page 86).

.

NOTE
The initialization process may last up to 15 minutes depending on the

actuator.

The initialization is complete when the following display appears:

The following display appears after pressing the operation mode key

briefly:

To exit the Configuration mode, press the operation mode key

for

longer than 5 s. The software version is displayed after about 5 s. The

instrument is in manual operation after releasing the operation mode

key.

.

NOTE
You can abort an ongoing initialization at any time by pressing the

operation mode key. Your previous settings are retained. All the para-

meters are reset to the factory setting only after performing a “Preset”.