Technical data 152 – Siemens SIPART PS2 6DR52xx User Manual

Page 152

Advertising
background image

Technical Data

152

SIPART PS2 Manual

A5E00074631--06

Accessory modules

Without Ex protection
(EEx d also)

With Ex protection EEx ia/ib

With Ex protection EEx n

Limit value contact module

6DR4004-8K

6DR4004-6K

6DR4004-6K

Limit transmitter with mechanical ground
contact and alarm output

Ex protection

without

II 2 G EEx ia/ib IIC T6

II 3 G EEx nA L [L] IIC T6

Max. switching current AC/DC

4 A

Connection to intrinsically safe
power circuits:

U

o

≤ 30 V

I

k

≤ 100 mA,

P

i

≤ 750 mW

Connection to intrinsically safe
power circuits:

U

o

≤ 30 V

I

k

≤ 100 mA,

P

i

≤ 750 mW

Max. switching voltage AC/DC

250 V / 24 V

30 V DC

30 V DC

Internal capacitance C

i

Negligible

Internal inductance L

i

Negligible

Electrical isolation

The 3 outputs are electrically isolated from the basic device

Test voltage

3150 V DC, 2s

3150 V DC, 2 s

3150 V DC, 2 s

Alarm module

See Alarm module

See Alarm module

See Alarm module

I

y

module

6DR4004-8J (without Ex protec-
tion)

6DR4004-6J (with Ex protection)

6DR4004-6J (with Ex protection)

DC output for position feedback

2-wire connection

2-wire connection

2-wire connection

Nominal signal range i

4 ... 20 mA, short-circuit-proof

4 ... 20 mA, short-circuit-proof

4 ... 20 mA, short-circuit-proof

Total operating range

3.6 ... 20.5 mA

3.6 ... 20.5 mA

3.6 ... 20.5 mA

Power supply U

H

+12 ... +35 V

+12 ... +30 V

+12 ... +30 V

External load R

B

[kW]

≤ (U

H

[V] - 12 V) /i [mA]

≤ (U

H

[V] - 12 V) /i [mA]

≤ (U

H

[V] - 12 V) /i [mA]

Transmission error

≤ 0.3%

≤ 0.3%

≤ 0.3%

Temperature effect

≤ 0.1%/10 K (≤ 0.1%/18 °F)

≤ 0.1%/10 K (≤ 0.1%/18 °F)

≤ 0.1%/10 K (≤ 0.1%/18 °F)

Resolution

≤ 0.1%

≤ 0.1%

≤ 0.1%

Residual ripple

≤ 1%

≤ 1%

≤ 1%

Internal capacitance C

i

≤ 11 nF

Internal inductance L

i

Negligible

For connection to power circuits with

Intrinsically safe: U

i

≤ 30 V DC

I

i

≤ 100 mA; P

i

≤ 1 W (only T4)

U

i

≤ 30 V DC

I

i

≤ 100 mA; P

i

≤ 1 W (only T4)

Electrical isolation

Electrically isolated from the
basic device

Electrically isolated from the
basic device

Electrically isolated from the
basic device

Test voltage

840 V DC, 1 s

840 V DC, 1 s

840 V DC, 1 s

NCS sensor

(not for EEx d version)

Position range

• Linear actuator

3 ... 130 mm (0.12 ... 5.12 inch),
to 200 mm (7.87 inch) on request

3 ... 130 mm (0.12 ... 5.12 inch),
to 200 mm (7.87 inch) on request

3 ... 130 mm (0.12 ... 5.12 inch),
to 200 mm (7.87 inch) on request

• Part-turn actuator

30° ... 100°

30° ... 100°

30° ... 100°

Linearity (after correction by SIPART PS2)
• Linear actuator

± 1%

± 1%

± 1%

• Part-turn actuator

± 1%

± 1%

± 1%

Hysteresis

± 0.2%

± 0.2%

± 0.2%

Continuous working temperature

-40 ... +85 °C (-40 ... +185 °F),
extended temperature range on
request

-40 ... +85 °C (-40 ... +185 °F),
extended temperature range on
request

-40 ... +85 °C (-40 ... +185 °F),
extended temperature range on
request

Degree of protection of casing

IP68/NEMA 4X

IP68/NEMA 4X

IP68/NEMA 4X

Advertising
This manual is related to the following products: