Design and Functional Principle

16

SIPART PS2 Manual

A5E00074631--06

spond even when the power supply fails or the electronics are defec-

tive.
The actuator can also be blocked or driven to its final positions depend-

ing on the configuration for example by an external event via a digital

input (DI2) on the alarm module.
If you require electrically independent limit value messages from the

standard controller, you will have to use the SIA module with the slot

initiators instead of the alarm module.
Communication with the controller is possible via the optional HART

interface.
To be able to use the positioner with a variety of different part-turn and

linear actuators, it has a friction clutch and switchable gearing.
The switchable gearing allows you to adjust the positioner for small and

large lifts. You can switch using the yellow switch (8, Fig. 2-11, page 28)

between 33_ (as delivered) and 90_.
The friction clutch (8, Fig. 2-11, page 28) allows you to set the working

range, particularly for linear actuators, after installation. You thus do not

have to ensure symmetrical mounting during the installation.
As it is not allowed to open the housing of an explosion-proof version in

a potentially explosive atmosphere, the shaft has an externally fitted,

additional friction clutch (8, Fig. 2-12, page 31).

NOTICE
for the explosion-proof version:
Only adjust the outer friction clutch (8, Fig. 2-12, page 31). The internal

friction clutch (8, Fig. 2-11 page 28) is fixed and, for the explosion-

proof version, must not be adjusted.