Operation

104

SIPART PS2 Manual

A5E00074631--06

Example:
YNRM = FLOW with YA = 10 % and YE = 80 %

YNRM = MPOS or YNRM = FLOW
Presetting:

YA = 0% and YE = 100%

Input current

(setpoint)

X display
W display

X display
W display

X display
W display

Mechan. Stroke
(actual value)

Mechan. Stroke

(actual value)

Mechan. Stroke
(actual value)

0mm

0mm

0mm

80mm

80mm

80mm

16mm

16mm

16mm

32mm

32mm

32mm

48mm

48mm

48mm

64mm

64mm

64mm

0%

0%

0%

100%

100%

100%

20%

20%

20%

40%

40%

40%

50%

50%

50%

60%

60%

60%

80%

80%

80%

YE = 80%

YE = 80%

YE = 100%

YA = 10%

YA = 10%

YA = 0%

Example:
YNRM = MPOS with YA = 10 % and YE = 80 %

4mA

20mA

7.2mA

10.4mA

13.6mA

16.8mA

Input current

(setpoint)

Input current

(setpoint)

4mA

20mA

7.2mA

10.4mA

13.6mA

16.8mA

4mA

20mA

7.2mA

10.4mA

13.6mA

16.8mA

Figure 4-10

Dependence on the stroke of standardization and on YA and YE in the example of an 80 mm
linear actuator

Manipulated variable direction of action
The direction of action (rising or falling) of the display and the position

feedback (Iy) can be set with this.

Tight closing with manipulated variable (see figure 4-9, page 102)
With this function the valve can be driven to the seat with the maximum

actuating force of the actuator (continuous contact of the piezo-valves).

The tight closing function can be activated on one side or for both limit

positions. YCLS becomes active when the setpoint is below the value

set with parameter “YCDO” or above that set with parameter “YCUP”.

38.YDIR

39.YCLS