Operation

129

SIPART PS2 Manual

A5E00074631--06

Short step zone up

and

Short step zone down
The short step zone is the range of the controller, in which pulse-

shaped excitation signals are output. The pulse length is proportional to

the control deviation. If the control deviation is not within the short step

zone, then the valves are activated in permanent contact.
These two parameters can be set for special applications (see chap-

ter 4.7, page 143).

Current temperature
Current temperature in the positioner housing. The sensor is on the

electronic circuit board.
The temperature display can be switched between _C and _F by

pressing the decrement button.

Minimum temperature (min/max pointer)

and

Maximum temperature (min/max pointer)
The minimum and maximum temperature in the housing interior is

determined continuously in the form of a min/max pointer and saved

and can only be reset at the factory.

Number of operating hours in temperature range T1 to T9
The device gives statistical information as to how long and in which

temperature ranges it was operated. For this purpose, the measured

temperature is averaged for each hour and the counter that is assigned

to the relevant temperature range is incremented every hour. This

allows conclusions to be made about past operating conditions of the

device and the entire control valve.
The temperature ranges are divided as follows:

T1

T2

T3

T4

T5

T6

T7

T8

T9

Temperature

range [_C]

≥--30

≥--30

<--15

≥--15

< 0

≥0

< 15

≥15

< 30

≥30

< 45

≥45

< 60

≥60

< 75

≥75

Number of switching operations pilot valve 1

and

Number of switching operations pilot valve 2
These two counters add up the activation processes of the pilot valves

and are for the assessment of the switching dependency.

26 SSUP

27 SSDN

28 TEMP

29 TMIN

30 TMAX

31 T1 to

39 T9

40 VENT1

41 VENT2