Siemens SIPART PS2 6DR52xx User Manual

Page 77

Advertising
background image

Preparing for Operation

77

SIPART PS2 Manual

A5E00074631--06

5.

Switch on to the following display

by pressing the operation

mode key twice:

6.

Start initialization by pressing the increment key

for longer

than 5 s.

Display:

7.

After 5 s the display changes to:

(The display of the potentiometer setting is shown here and below

as an example only).

Now move the actuator to the position which you want to define as
the first of the two end positions with the increment

and decre-

ment

key. Then press the operation mode key

. This accepts

the current position as end position 1 and switches on to the next

position.

.

NOTE
If the message “RANGE” appears in the bottom line, the selected end

position is outside the permissible measuring range. There are several

ways to correct the error:
S

Adjust the friction clutch until “OK” appears and press the operation

mode key again or

S

move to another end position with the increment and decrement key

or

S

abort initialization by pressing the operation mode key. You then have

to change to P manual operation and correct the travel and the posi-

tion detection according to step 1.

Advertising
This manual is related to the following products: