Technical data 149 – Siemens SIPART PS2 6DR52xx User Manual

Page 149

Advertising
background image

Technical Data

149

SIPART PS2 Manual

A5E00074631--06

Technical specifications

SIPART PS2

Basic device
without Ex protection

Basic device
with EEx-d protection
(flameproof casing)

Basic device
with EEx ia/ib protection

Basic device
with EEx n protection

Explosion protection to
EN 50014, EN 50020 and EN 50021

Without

EEx d
II 2 G EEx d II C T6

EEx ia/ib
II 2 G EEx ia/ib II C T6

EEx n
II 3 G EEx nA L [L] II C T6

Mounting location

Zone 1

Zone 1

Zone 2

Permissible ambient temperature for
operation

At

≤ -10 °C (+14 °F) the display refresh

rate of the LCD is limited.

(for basic devices with EEX ia/ib and
EEx n protection the following applies:
Only T4 is permissible when using I

y

module.)

-30 ... +80 °C
(-22 ... +176 °F)

T4: -30 ... +80 °C (-22 ... +176 °F)

T5: -30 ... +65 °C (-22 ... +149 °F)

T6: -30 ... +50 °C (-22 ... +122 °F)

Electrical data

Input

2-wire connection (terminals 6/8)

Rated signal range

4 ... 20 mA

4 ... 20 mA

4 ... 20 mA

4 ... 20 mA

Current to maintain the power supply

≥ 3.6 mA

≥ 3.6 mA

≥ 3.6 mA

≥ 3.6 mA

Required load voltage
U

B

(corresponds to

Ω at 20 mA)

• Without HART (6DR50..)

- Typical

6.36 V (corresponds to
318

Ω)

6.36 V (corresponds to
318

Ω)

7.8 V (corresponds to
390

Ω)

7.8 V (corresponds to
390

Ω)

- Max.

6.48 V (corresponds to
324

Ω)

6.48 V (corresponds to
324

Ω)

8.3 V (corresponds to
415

Ω)

8.3 V (corresponds to
415

Ω)

• Without HART (6DR53..)

- Typical

7.9 V (corresponds to
395

Ω)

- Max.

8.4 V (corresponds to
420

Ω)

• With HART (6DR51..)

- Typical

6.6 V (corresponds to
330

Ω)

6.6 V (corresponds to
330

Ω)

- Max.

6.72 V (corresponds to
336

Ω)

6.72 V (corresponds to
336

Ω)

• With HART (6DR52..)

- Typical

8.4 V (corresponds to
420

Ω)

8.4 V (corresponds to
420

Ω)

8.4 V (corresponds to
420

Ω)

- Max.

8.8 V (corresponds to
440

Ω)

8.8 V (corresponds to
440

Ω)

8.8 V (corresponds to
440

Ω)

• Static destruction limit

± 40 mA

Internal capacitance C

i

• Without HART

≤ 22 nF

• With HART

≤ 7 nF

Internal inductance L

i

• Without HART

≤ 0.12 mH

• With HART

≤ 0.24 mH

For connection to power circuits with

intrinsically safe
U

o

≤ 30 V DC

I

k

≤ 100 mA

P

≤ 1 W

U

i

≤ 30 V DC

I

i

≤ 100 mA

Advertising
This manual is related to the following products: