Siemens SIPART PS2 6DR52xx User Manual

Page 135

Advertising
background image

Operation

135

SIPART PS2 Manual

A5E00074631--06

9

Partial stroke test exceeds reference step time
This error message appears on the one hand if a manual or cyclic

partial stroke test is triggered and the test cannot be started because

the valve is not within the start tolerance range. The error message

also appears if one of the three thresholds of the partial stroke test that

are a result of the reference step time (A6.PSTIN) times factors

(A7.FACT1 to A9.FACT3) is violated. How serious the error message

is, can be seen at the bar graph on the right side of the display. At the

same time, the severity of the error message is output via the fault

message output or the alarm outputs, according to the operating mode

of the extended diagnostics.

10

General control valve malfunction
The monitoring of the operational behavior triggers if the actual valve

position leaves a narrow corridor between guide value and expected

position sequence. In this case, the deviation between expected and

actual position sequence is filtered and output and compared to the set

thresholds that are the result of the limit (b2.LIMIT) times the factors

(b3.FACT1 to b5.FACT3).

11

Pneumatic leakage
This error message appears if the leakage indicator exceeds the set

thresholds. Note that the function can only take effect with its entire

sensitivity if a ramp test is performed to set the leakage indicator after

initialization (see Explanations on C1.LIMIT).

12

Slipstick effect too high
If the slipstick of the control valve is increased during operation of if an

increasing number of slip jumps are detected, the relevant limits can be

exceeded, resulting in an error message.

13

Temperature fallen short of
This error message appears if the lower temperature limit thresholds

are fallen short of.

14

Temperature exceeded
This error message appears if the upper temperature limit thresholds

are exceeded.

15

Monitoring of the position average
If a position average is calculated when a comparison interval passes

that deviates from the reference value by more than the set thresholds,

this error message triggers.

Advertising