Operation

128

SIPART PS2 Manual

A5E00074631--06

Average position value
The comparison average calculated last is displayed here. There are

also the following status messages:

S

OFF

The basic function is deactivated in the configuration menu.

S

IdLE (inactive)

The function has not been started yet.

S

rEF (reference average is calculated)

The function was started and the reference interval is currently

active.

S

COMP (comparison average is calculated)

The function was started and the comparative interval is currently

active.

Potentiometer value lower stop

and

Potentiometer value upper stop
These two values indicate the measured values of the position

displacement sensor (potentiometer) at the lower or upper limit stop,

as determined during the automatic initialization. With manual initializa-

tion, the values of the manually approached end positions can be found

here.

Pulse length up

and

Pulse length down
During the initialization phase, the smallest pulse lengths are deter-

mined, with which a movement of the actuator can be achieved.

They are determined separately for the “Up” direction and the “Down”

direction and displayed here.
These two parameters can be set for special applications (see chap-

ter 4.7, page 143).

Dead zone up

and

Dead zone down
The dead zone of the controller in “Up” direction or in “Down” direction

is displayed here. The values correspond either to the manually set

value of parameter “34.DEBA” or to the value automatically adapted by

the device if “DEBA” was set to “Auto”.

19 PAVG

20 P0

21 P100

22 IMPUP

23 IMPDN

24 DBUP

25 DBDN