Siemens SIPART PS2 6DR52xx User Manual

Page 110

Advertising
background image

Operation

110

SIPART PS2 Manual

A5E00074631--06

Partial stroke test
This parameter activates the partial stroke test for the cyclic or manual

partial stroke test of Up/Down and modulating valves.
The partial stroke test can be triggered via keyboard, a binary input or

the HART communication.

Start position
The start position of the partial stroke test is specified here within the

range of 0.0 to 100.0%.

Start tolerance
The start tolerance in relation to the start position is specified here in

the range of 0.1 to 10.0%. That means, with a start position of e.g. 50%

and a start tolerance of 2%, a partial stroke test can only be triggered

during operation if the current position is between 48 and 52%.

Step height
Input of the step height of the partial stroke test within the range of

0.1 to 100.0%. The factory setting is 10.0%.

Step direction
Input of the step direction of the partial stroke test. The following

options are available:

“up”, “do” (down), “up do” (up and down). If “up” is selected, the

actuator is moved in a controlled manner from its start position to the

target position (start position + step height) and then back to the

original position in a controlled way once the target position has been

reached. The procedure for the “do” option is the same but in the

opposite direction. With “up do”, the actuator first travels in a controlled

manner from its start position to the upper target position (start position

+ step height), then controlled from the upper to the lower target

position (start position -- step height). After reaching the lower target

position, it returns to its original position in a controlled manner.

Test interval
Input of the interval for the cyclic partial stroke test within the range of

one day to 365 days.

A. PST

A1.STPOS

A2.STTOL

A3.STEP

A4.STEPD

A5.INTRV

Advertising
This manual is related to the following products: