6 meaning of the other display text – Siemens SIPART PS2 6DR52xx User Manual

Page 139

Advertising
background image

Operation

139

SIPART PS2 Manual

A5E00074631--06

Fault indication

(symptoms)

possible cause(s)

Remedies

Zero point misadjusts

sporadically (> 3 %).

Stress caused by knocks or

shocks result in acceleration

values that are so high that the

friction clutch is misadjusted

(e.g. with “steam pulses” in

steam lines)

Eliminate causes of shock

stress.

Re-initialize positioner.

Complete device function

failure: also no indication in

the display

Electrical power supply

insufficient

Check electrical power supply.

In the event of continuous high

vibration stress (vibrations):

Screws on the electrical

connecting terminals can

loosen.

Electrical connecting terminals

and/or electronic components

can loosen due to vibrations.

Tighten screws and secure

them with locking varnish.

Repair (see chapter 5,

page 145)

For prevention purposes:

Fit SIPART PS 2 on shock

mounts.

Table 9

4.6 Meaning of the other display text

Remarks on the tables:

nn

stands for variable numerical values

Error symbol

/

(slash): the text segments to the left and right of the-

slash flash alternately

Messages before the installation phase (initial start-up):

Upper lin

e

Lower lin

e

Meaning/cause

Measure

CPU

START

x

x

Message after applying the electrical

power supply

S

Wait

P nnn.n

x

Potentiometer voltage when

positioner is not initialized (P manual

mode) (actual position value in % of

measuring range)

S

Check with the “+” and “--” buttons
whether the entire actuator travel can
be moved along and that “P------” is
never displayed

S

Perform initialization

P------

x

Measuring range exceeded,

potentiometer is in the inactive zone,

switch transmission ratio selector or

effective lever arm have not been

adapted to the actuator travel

S

Switch transmission ratio selector to
90 degrees for part-turn actuators

S

Adjust effective lever length for linear
actuators to measuring range

NOINI

x

Positioner is not initialized

S

Start initialization

Advertising
This manual is related to the following products: