5 service and maintenance, Service and maintenance – Siemens SIPART PS2 6DR52xx User Manual

Page 145

Advertising
background image

Care and Maintenance

145

SIPART PS2 Manual

A5E00074631--06

Service and Maintenance

The positioner is largely maintenance-free. The positioners are fitted

with filters in the pneumatic connections as protection against coarse

particles of dirt. If the pneumatic energy supply contains particles of

dirt, the filters may clog and impair the function of the positioner. In this

case the filters can be cleaned as follows.

Positioner in metal housing and explosion proof version

1. Switch off the pneumatic power supply and remove the pipes.

2. Remove the metal filters carefully from the holes and clean

(e.g. with compressed air).

3. Insert the filters.

4. Re-connect the pipes and supply pneumatic energy.

Positioner in plastic housing
Removal

1. Switch off the pneumatic power supply and remove the pipes.

2. Unscrew the cover

3. Remove the three screws from the pneumatic connector strip.

4. Remove the filters and O-rings behind the connector strip.

5. Clean the filters (e.g. with compressed air).

Installation

6. First insert the filters in the recesses in the plastic housing and then

place the O-rings on the filters.

7. Align the pneumatic connector strip on the two lugs and screw tight

with the three self--tapping screws.

Important:

Make sure that the same thread is used. To do this turn the screws

counterclockwise until they snap into the thread audibly. Only then

should you tighten the screws.

5

Advertising
This manual is related to the following products: