4 mounting kit, 6 restrictors – Siemens SIPART PS2 6DR52xx User Manual

Page 22

Advertising
background image

Design and Functional Principle

22

SIPART PS2 Manual

A5E00074631--06

2.3.4 Mounting Kit

The positioner can be mounted on almost all actuators with the ap-

propriate mounting kit.

2.3.5 Purge air switching (not in the explosion proof version)

The purge air switch is accessible above the pneumatic terminal strip

with the housing open (figure 2-7). In the IN position the inside of the

housing is purged with very small amounts of clean, dry instrument air.

In the OUT position the purge air is fed directly to the outside air.

Figure 2-7

Purge air switch on the valve block, view of the positioner onto pneumatic connection side
with cover open

2.3.6 Restrictors

In order to achieve travel times of > 1.5 s in small actuators, the air rate

can be reduced with the restrictors Y1 and Y2 (figure 2-8, in explosion

proof version, see figure 2-5, page 19). By turning to the right the air

rate is reduced up to shutting off. To set the restrictors it is advisable to

close them and then open them slowly (see initialization RUN3).
In the case of double-acting valves make sure that both chokes are set

approximately equal.

Y1 Y2

Hexagon socket 2.5 mm

Figure 2-8

Restrictors

Advertising
This manual is related to the following products: