2.7.2 Installation of options modules in explosion proof version

The following option modules are available for the positioner in the ex-

plosion-proof version:

--

Iy

-module

-- Alarm module

The options modules are protected and mechanically fixed by a module

cover ((1), see figure 2-12, page 31).

.

NOTE
The housing must be opened to install the options modules. The

degree of protection IP66/NEMA4x is not guaranteed as long as the

positioner is open.

!

WARNING
In areas in which the atmosphere may be potentially explosive, the

explosion-proof positioner may only be supplied with electrical auxiliary

power when the housing is closed and when built-in, approved elec-

tronics are used.
The feed-though openings for the electronic connections must be

sealed with EEX-d certified cable glands or EEx-d certified plugs or

an ignition lock must be mounted at a maximum distance of 46 cm

(18 inches) when using the “conduit”-system.

See figure 2-12, page 31. Disconnect or isolate the power supply

cables first.
To open the positioner, the safety catch (12) must be opened and the

screw-on cover unscrewed.
After loosening the four fixing screws (13.1) the complete rack (13) can

be removed. The actuator may have to be turned so that the clutch can

be easily disengaged.
Remove the module cover (1). To do this, the two screws (1.1) must be

removed with a screwdriver.

Installation

Open the

positioner