background image

Design and Functional Principle

32

SIPART PS2 Manual

A5E00074631--06

Insert the I

y

module (3) in the lower slot of the rack up to the stop and

use the 6-pin flat ribbon cable (6) provided to connect it to the

motherboard (see figure 2-11, page 28).

2.7.4 Alarm module

The alarm module contains

S

3 digital outputs and

S

1 digital input

The digital outputs serve to output fault messages and alarms. The

configuration is described in chapter 4.4, page 95, with the para-

meters 44 to 54.
By an external signal applied at digital input (DI2) the actuator can be

blocked or driven to its limit positions for example depending on the

configuration. The configuration is described in chapter 4.4, page 95,

with the parameters 43.
The alarm module is available in two versions:

S

explosion protected for connecting to switching amplifier

EN 60947-5-6

S

non-explosion protected for connection to voltage sources with a

maximum 35 V

The semiconductor outputs of the alarm module report an alarm (signal

state Low) by switching off with high resistance. They are conductive in

the High state (without alarm). The dynamic control makes them error

self-reporting.
The outputs are potentially isolated from the basic circuit and each

other.
The digital input is double.

S

one potential isolated for voltage level

S

one not potential isolated for floating contacts

These two inputs are designed as logic OR links.

Insert the alarm unit (4) below the motherboard in the rack up to the

stop and use the 8-pin flat ribbon cable (5) to connect it to the mother-

board (see figure 2-11, page 28).

Installation

Function

Installation