Preparing for Operation

59

SIPART PS2 Manual

A5E00074631--06

.

NOTE
Use standard M20 x 1.5 cable gland nuts to ensure leakage (IP-protec-

tion of the housing) and for the necessary tensile strength use only

cables with a cable diameter ≥ 8 mm, or for smaller diameters use a

suitable sealing insert.

For the NPT version, the positioner will be delivered with an adapter.

Make sure that when fitting a part into the adapter, that the maximum

permissible torque of 10 Nm is not exceeded.

NOTE for use in zone 2:
Non-sparking equipment for Zone 2 may not be connected or discon-

nected under power in normal operation.
However, during installation or repair work the positioner may be con-

nected or disconnected even under power (see also certificate for

zone 2).

NOTE for use in two-wire systems:
Never connect the current input (terminal 6 and 7) to a voltage source

as this could destroy the positioner.
Always use a current source with a maximum output current of 20 mA.
To maintain the power supply, the input current must be ≥3.6 mA.

3.4.1 Connection in non-intrinsically safe and explosion proof version

+

J

4 to 20 mA

Positioner

Digital input 1

6
7
8
9
10

Only for:
6DR51x0-xNxxx

6DR5111-xNxxx

6DR51x5-xExxx

HART Communicator

A

E

6DR50x0-xNxxx

6DR5011-xNxxx

6DR51x0-xNxxx

6DR5111-xNxxx

6DR50x5-xExxx

6DR51x5-xExxx

Figure 3-13

Two-wire connection